Power Factor Correction Calculator

Calculate required capacitor bank kVAR and μF to improve power factor. Qc = P × (tan φ₁ − tan φ₂).

kVAR Sizing Capacitor μF Power Triangle
Quick presets

Results

Required Capacitor Bank
Capacitance per Phase
Current Before (S₁ / I₁)
Current After (S₂ / I₂)
Current Reduction

Reactive Power Compensation

Capacitance in μF

Example — 100 kW load, PF 0.75 → 0.95

tan φ₁ = tan(acos 0.75) = 0.8819, tan φ₂ = tan(acos 0.95) = 0.3287

Qc = 100 × (0.8819 − 0.3287) = 55.3 kVAR

⚠️ Note: Do not overcorrect above unity PF (leading). This can cause voltage rise, resonance with transformers, and equipment damage.