Free Engineering Tool
Cable Cross-Section Calculator
Determine the correct wire size (mm²) based on current, cable length, voltage, and allowable voltage drop. Round up to nearest standard IEC size automatically.
Results
Cable Cross-Section Formula
The minimum required conductor cross-section to stay within the allowable voltage drop is:
- k — system factor: 2 for single-phase AC and DC, √3 for three-phase AC
- ρ — resistivity of conductor (Ω·mm²/m): Cu = 0.0175, Al = 0.0283
- I — current (A)
- L — one-way cable length (m)
- Vdrop — allowable voltage drop (V)
Allowable Voltage Drop
Actual Voltage Drop
Once a standard cable size Astd is selected:
Standard Cable Sizes (IEC 60228)
| mm² | AWG (approx.) | mm² | AWG (approx.) |
|---|---|---|---|
| 0.75 | 18 AWG | 25 | 4 AWG |
| 1.0 | 17 AWG | 35 | 2 AWG |
| 1.5 | 15 AWG | 50 | 1/0 AWG |
| 2.5 | 13 AWG | 70 | 2/0 AWG |
| 4 | 11 AWG | 95 | 3/0 AWG |
| 6 | 9 AWG | 120 | 4/0 AWG |
| 10 | 7 AWG | 150 | 300 MCM |
| 16 | 5 AWG | 185 | 350 MCM |
Practical Example
Given: I = 10 A, L = 30 m, V = 230 V, max drop = 3%, copper
Vdrop(allowed) = 230 × 3/100 = 6.9 V
A = 2 × 0.0175 × 10 × 30 / 6.9 = 1.52 mm²
Standard size: 2.5 mm² (rounded up)
Actual Vdrop = 2 × 0.0175 × 10 × 30 / 2.5 = 4.2 V = 1.83%
⚠️ Note: This calculator sizes cable based on voltage drop only. Always verify that the selected cable size also meets the current-carrying capacity (ampacity) requirements per local electrical codes (e.g., IEC 60364, NEC).
Professional field balancing instruments and software. Used in 50+ countries for industrial maintenance.