Generator Bearing Temperature Monitor & Limits
Suriin ang bearing temperature laban sa alarm at trip limits per IEEE C50.13 at manufacturer guidelines. Sinusuportahan ang journal at rolling element bearings na may iba't ibang lubricant types.
Results
IEEE C50.13 Bearing Temperature Limits
IEEE C50.13 (Cylindrical-Rotor Synchronous Generators) ay nagbibigay ng gabay sa bearing temperature limits para sa generators. Ang mga sumusunod ay tipikal na limits:
| Bearing Type | Normal (°C) | Alarm (°C) | Trip (°C) | Max ΔT (°C) |
|---|---|---|---|---|
| Journal (sleeve), mineral oil | ≤ 75 | 90 | 100 | 45 |
| Journal (sleeve), synthetic oil | ≤ 80 | 95 | 105 | 50 |
| Rolling element, grease | ≤ 70 | 80 | 95 | 40 |
| Rolling element, oil bath | ≤ 75 | 85 | 100 | 45 |
Pagtaas ng Temperatura (ΔT)
Ang temperature rise na higit sa ambient ay isang pangunahing diagnostic indicator:
- ΔT ≤ 40°C — Normal operation
- ΔT = 40–55°C — Mataas — imbestigahan ang sanhi
- ΔT > 55°C — Sobrang taas — kailangan ng agarang aksyon
Karaniwang Dahilan ng Mataas na Bearing Temperature
- Hindi sapat o nabawasang pampadulas
- Maling pagkakahanay (angular o offset)
- Labis na pagkarga o preload ng bearing
- Napapakompromisong oil flow o cooling
- Sirang bearing (spalling, scoring)
- Alitan ng shaft seal
- Mataas na temperatura ng kapaligiran
ℹ️ Trend interpretation: Ang biglaang pagtaas ng temperatura na 10°C o higit pa sa loob ng maikling panahon (oras) ay nagpapahiwatig ng isang umuusbong na problema at nangangailangan ng agarang imbestigasyon, kahit na ang absolute temperature ay nasa ibaba ng alarm level.
⚠️ Note: Ito ay tipikal na industry limits. Laging basahin ang specific generator manufacturer’s documentation para sa exact alarm at trip setpoints, dahil maaaring iba batay sa bearing design, size, at operating conditions.