What is an Alarm Level? Vibration Threshold Setting • Portable balancer, vibration analyzer "Balanset" for dynamic balancing crushers, fans, mulchers, augers on combines, shafts, centrifuges, turbines, and many others rotors What is an Alarm Level? Vibration Threshold Setting • Portable balancer, vibration analyzer "Balanset" for dynamic balancing crushers, fans, mulchers, augers on combines, shafts, centrifuges, turbines, and many others rotors

Understanding Alarm Levels

Portable balancer & Vibration analyzer Balanset-1A

Vibration sensor

Optical Sensor (Laser Tachometer)

Balanset-4

Dynamic balancer “Balanset-1A” OEM

Definition: What is an Alarm Level?

Alarm level (also called alarm threshold, alarm limit, or alarm setpoint) is a predefined vibration value that, when exceeded, triggers an alert, notification, or automated action in a condition monitoring system. Alarm levels define the boundaries between acceptable and unacceptable equipment operation, automatically flagging conditions requiring investigation or intervention. They transform continuous streams of measurement data into actionable information by highlighting exceptions that demand attention.

Proper alarm level setting is critical to monitoring program success—too sensitive creates alarm fatigue from false alerts, too lenient misses real problems until advanced stages. Effective alarm levels balance early detection with practical response capabilities, incorporating equipment criticality, historical data, and industry standards.

Multi-Level Alarm Philosophy

Typical Alarm Structure

Normal Range

  • Below Alert Level: Equipment healthy
  • Action: Continue routine monitoring
  • Typical: < 1.5-2× baseline or < ISO Zone B limit

Alert (Caution)

  • Level: 2-3× baseline or entering ISO Zone C
  • Meaning: Condition degrading, investigate cause
  • Action: Increase monitoring frequency, plan inspection, identify trend
  • Timeline: Maintenance within weeks to months

Alarm (Warning)

  • Level: 4-6× baseline or upper Zone C
  • Meaning: Significant problem, urgent attention needed
  • Action: Schedule maintenance soon (days to weeks), detailed diagnosis, monitor daily
  • Timeline: Repair within 1-4 weeks

Danger (Critical)

  • Level: 8-10× baseline or entering ISO Zone D
  • Meaning: Severe condition, imminent failure risk
  • Action: Plan immediate shutdown and repair
  • Timeline: Days, continuous monitoring until repair

Trip (Shutdown)

  • Level: Catastrophic failure imminent
  • Meaning: Equipment must be stopped to prevent damage
  • Action: Automatic or immediate manual shutdown
  • Implementation: Online monitoring with automatic shutdown capability

Alarm Setting Methods

1. Baseline-Referenced Alarms

Machine-specific based on historical data:

  • Alert: 2× baseline
  • Alarm: 4× baseline
  • Danger: 8× baseline
  • Advantage: Customized to each machine’s normal operation
  • Requirement: Good baseline data essential

2. Standards-Based Alarms

Using ISO 20816 or industry standards:

  • Zone boundaries define alarm levels
  • Based on machine type and size
  • Advantage: Standardized, widely accepted
  • Limitation: May not match specific machine characteristics

3. Statistical Alarms

  • Based on mean and standard deviation of historical data
  • Alert: Mean + 2σ
  • Alarm: Mean + 3σ
  • Advantage: Adapts to machine variability
  • Requirement: Sufficient historical data

4. Component-Specific Alarms

  • Separate limits for different spectrum components
  • 1× alarm for unbalance
  • Bearing frequency alarms
  • Gear mesh frequency alarms
  • Advantage: Specific fault detection

Alarm Response Procedures

Alert Level Response

  • Review trend to confirm not false alarm
  • Increase monitoring frequency
  • Review recent maintenance or operating changes
  • Plan more detailed analysis
  • Continue operation with monitoring

Alarm Level Response

  • Detailed vibration analysis (FFT, envelope)
  • Identify specific fault
  • Generate work order
  • Schedule maintenance (1-4 weeks)
  • Monitor daily or continuously until repair

Danger/Trip Response

  • Immediate engineering assessment
  • Plan rapid shutdown and repair
  • Prepare spare parts and resources
  • Consider whether continued operation safe
  • Execute repair at first opportunity

Common Alarm Setting Mistakes

Too Sensitive

  • Frequent false alarms
  • Alarm fatigue (operators ignore alarms)
  • Wasted investigation time
  • Loss of credibility

Too Lenient

  • Problems reach advanced stages before detection
  • Reduced lead time for planning
  • Higher repair costs
  • Risk of failures

One-Size-Fits-All

  • Same alarm for all equipment types
  • Doesn’t account for machine differences
  • Either too many false alarms or missed problems
  • Machine-specific alarms preferred

Optimization and Tuning

Initial Settings

  • Start with conservative (tighter) alarms
  • Based on standards or baseline × factors
  • Monitor false alarm rate
  • Adjust after gaining experience

Refinement

  • Track alarm performance (true vs. false)
  • Adjust limits based on false alarm rate
  • Target: < 5-10% false alarms
  • Document changes and rationale

Continuous Improvement

  • Learn from missed failures (alarms too lenient)
  • Learn from false alarms (too sensitive)
  • Incorporate new data and experience
  • Periodic alarm level review (annually)

Alarm levels are the decision boundaries that convert condition monitoring measurements into actionable information. Proper alarm setting—balancing sensitivity with specificity, matching levels to equipment criticality and deterioration rates, and continuously refining through experience—is essential for monitoring program effectiveness, ensuring real problems are detected early while avoiding alarm fatigue from excessive false alerts.