Proximity Probe Gap Voltage Calculator
Calculate eddy current probe gap voltage, gap distance from voltage, and verify linear operating range. For shaft vibration and position measurement setup per API 670.
Results
Gap Voltage Relationship
Output is negative voltage (larger gap → more negative). Standard sensitivity: 7.87 mV/μm = 200 mV/mil.
Linear Ranges by Probe Size
| Probe | Linear Range (mm) | Linear Range (mil) | Voltage Range |
|---|---|---|---|
| 5 mm | 0.25 – 1.30 | 10 – 50 | −2 to −10 V |
| 8 mm | 0.25 – 2.30 | 10 – 90 | −2 to −18 V |
| 12 mm | 0.50 – 4.00 | 20 – 160 | −4 to −32 V |
Given: 8 mm probe, 7.87 mV/μm, 4140 steel target
Target gap = 1.27 mm = 1270 μm → V = −7.87 × 1270 / 1000 = −9.99 V DC ≈ −10 V
Linear range: 0.25–2.30 mm → 1.27 mm is centered ✓
⚠️ Note: Non-steel targets require sensitivity correction. Operating outside the linear range causes measurement errors > 5%.