Free Engineering Tool
Motor Starting Current Calculator
Calculate motor starting (inrush) current for DOL, star-delta, soft starter, and VFD methods. Istart = kstart × Irated.
DOL 6–8×
Star-Delta 2–3×
VFD 1–1.5×
Results
Starting Current I_start
—
Rated Full-Load Current I_rated
—
Start Multiplier k
—
Starting Apparent Power
—
Starting Method
—
Rated Current
Starting Current
Starting Methods Comparison
| Method | Current Multiplier | Torque | Typical Use |
|---|---|---|---|
| DOL | 6–8 × Irated | Full | Small motors < 7.5 kW |
| Star-Delta | 2–3 × Irated | ~33% | Pumps, fans, 7.5–75 kW |
| Soft Starter | 2–4 × Irated | Variable | Conveyors, compressors |
| VFD | 1–1.5 × Irated | Full | Any, best control |
Example — 15 kW Motor, DOL Start
Given: P = 15 kW, V = 400 V, cos φ = 0.85, η = 0.91, DOL k = 7
Irated = 15000 / (√3 × 400 × 0.85 × 0.91) = 28.0 A
Istart = 7 × 28.0 = 196.0 A