Motor Starting Current Calculator

Calculate motor starting (inrush) current for DOL, star-delta, soft starter, and VFD methods. Istart = kstart × Irated.

DOL 6–8× Star-Delta 2–3× VFD 1–1.5×
Quick presets

Results

Starting Current I_start
Rated Full-Load Current I_rated
Start Multiplier k
Starting Apparent Power
Starting Method

Rated Current

Starting Current

Starting Methods Comparison

MethodCurrent MultiplierTorqueTypical Use
DOL6–8 × IratedFullSmall motors < 7.5 kW
Star-Delta2–3 × Irated~33%Pumps, fans, 7.5–75 kW
Soft Starter2–4 × IratedVariableConveyors, compressors
VFD1–1.5 × IratedFullAny, best control
Example — 15 kW Motor, DOL Start

Given: P = 15 kW, V = 400 V, cos φ = 0.85, η = 0.91, DOL k = 7

Irated = 15000 / (√3 × 400 × 0.85 × 0.91) = 28.0 A

Istart = 7 × 28.0 = 196.0 A