Libreng Kasanayan sa Inhinyero
Kalkulador ng Kasiguradong Agos ng Motor
Kalkulahin ang simula ng agos ng kuryente (inrush) ng motor para sa mga pamamaraan ng DOL, star-delta, soft starter, at VFD. Istart = kstart × Irated.
DOL 6–8×
Star-Delta 2–3×
VFD 1–1.5×
Results
Starting Current I_start
—
Rated Full-Load Current I_rated
—
Start Multiplier k
—
Nagsisimulang Apparent Power
—
Starting Method
—
Rated Current
Starting Current
Paghahambing ng mga Pamamaraan ng Pagsisimula
| Method | Current Multiplier | Torque | Typical Use |
|---|---|---|---|
| DOL | 6–8 × Irated | Full | Maliit na mga motor < 7.5 kW |
| Star-Delta | 2–3 × Irated | ~33% | Mga pump, fan, 7.5–75 kW |
| Soft Starter | 2–4 × Irated | Variable | Mga conveyor, compressor |
| VFD | 1–1.5 × Irated | Full | Anuman, pinakamahusay na kontrol |
Halimbawa — 15 kW Motor, DOL Start
Given: P = 15 kW, V = 400 V, cos φ = 0.85, η = 0.91, DOL k = 7
Irated = 15000 / (√3 × 400 × 0.85 × 0.91) = 28.0 A
Istart = 7 × 28.0 = 196.0 A
Vibromera — Portable Balancing & Vibration Analysis
Mga propesyonal na instrumento at software para sa field balancing. Ginagamit sa mahigit 50 bansa.
Learn More
Mga propesyonal na instrumento at software para sa field balancing. Ginagamit sa mahigit 50 bansa.
Categories: