Kalkulahin ang simula ng agos ng kuryente (inrush) ng motor para sa mga pamamaraan ng DOL, star-delta, soft starter, at VFD. Istart = kstart × Irated.

DOL 6–8× Star-Delta 2–3× VFD 1–1.5×
Quick presets

Results

Starting Current I_start
Rated Full-Load Current I_rated
Start Multiplier k
Nagsisimulang Apparent Power
Starting Method

Rated Current

Starting Current

Paghahambing ng mga Pamamaraan ng Pagsisimula

MethodCurrent MultiplierTorqueTypical Use
DOL6–8 × IratedFullMaliit na mga motor < 7.5 kW
Star-Delta2–3 × Irated~33%Mga pump, fan, 7.5–75 kW
Soft Starter2–4 × IratedVariableMga conveyor, compressor
VFD1–1.5 × IratedFullAnuman, pinakamahusay na kontrol
Halimbawa — 15 kW Motor, DOL Start

Given: P = 15 kW, V = 400 V, cos φ = 0.85, η = 0.91, DOL k = 7

Irated = 15000 / (√3 × 400 × 0.85 × 0.91) = 28.0 A

Istart = 7 × 28.0 = 196.0 A