VFD Continuous and Overload Rating Comparator
For one motor, one identified variable-frequency drive and one documented operating configuration. The tool compares current ratings that you copy from an engineering load study and the current manufacturer data; it does not select a VFD model or frame size.
Controlled comparison record
All enabled fields are required. Decimal point and decimal comma are accepted; grouped numbers, exponents and unit suffixes are rejected.
Equations and interpretation
Continuous current
DeltaI = Idrive,derated – Irequired
Margin% = 100 x DeltaI / Irequired
Irequired is the continuous output-current requirement from the documented application study. Idrive,derated is the selected product’s continuous output-current rating after every applicable manufacturer derating. The arithmetic boundary is Rcont >= 1. Equality leaves no numerical current margin and is not an engineering approval.
One overload point
Rtime = tdrive,allowed / trequired
The point meets this limited arithmetic screen only when both ratios are at least 1. The recurrence, cooldown, shape of the current/torque profile and the complete manufacturer overload curve still require separate review. A drive can satisfy one point and fail the actual duty cycle.
Why motor kW is not converted into a “required VFD current” here
The familiar expression P/(sqrt(3) V power-factor efficiency) is a balanced three-phase sinusoidal power relation under stated assumptions. It is not a universal VFD selection formula, does not apply unchanged to single-phase input, and cannot replace motor nameplate data, a torque-speed study or product-specific output-current and derating limits. Input current and output current are also different rating quantities.
Source and standard record
| Извор | Status checked 16 Jul 2026 | What it supports here | What it does not support |
|---|---|---|---|
| IEC 61800-2:2021, Edition 3.0 | Valid; published 2021-03-03; stability date 2027. | General rating specifications and criteria to consider when selecting AC power-drive-system attributes. | No universal motor-kW-to-drive-frame table and no fixed ND/HD multiplier for every product. |
| IEC 61800-5-1:2022, Edition 3.0 | Valid; corrigenda 1:2023 and 2:2025 included in the official copy; stability date 2026. | Electrical, thermal and energy safety scope for power-drive systems. | Not a shortcut for application sizing or a substitute for the selected manufacturer’s ratings. |
| IEC 61800-3:2022, Edition 4.0 | Valid; official copy includes Corrigendum 1:2025. | EMC is a separate system-level requirement that must be reviewed. | This comparator does not perform an EMC assessment. |
| ABB Technical Guide No. 7, Dimensioning of a drive system, 2011, pp. 26 and 31 | Official manufacturer guide; used as an engineering explanation, not as a current product catalog. | Selection considers torque characteristics, converter current limits, supply voltage and derating; p. 31 illustrates a continuous-current requirement. | Its example values are not universal ratings and must not be copied to another application or product. |
| Danfoss VLT AutomationDrive FC 301/302 Design Guide, document shown as AJ286655760917en-000101 / 130R0301, 2019.10, pp. 94, 96, 98, 130-131 | Official product guide retained as a product-specific illustration; use the current revision for an actual selection. | Continuous and intermittent output-current ratings vary by type code, supply-voltage range and duty; derating varies with altitude, temperature, switching frequency and enclosure. | The illustrated 110%, 150% or 160% values are not universal VFD rules. |
Published boundary example
The example button copies one product-specific catalog boundary from the Danfoss guide, page 98: FC 301/302 T4/T5 type P7K5 in the high-overload 380-440 V row lists 16 A continuous and 25.6 A intermittent; the table heading specifies one minute per ten minutes. The example sets both requirements equal to those catalog limits only to test equality handling. It deliberately leaves all confirmations unchecked. It is not a recommendation for that drive or for any real motor.
Limits that remain outside this comparator
- Full torque-speed/loadability envelope, field weakening, acceleration time, motor and load inertia, starting and breakaway torque.
- Overload curve, repetition/cooldown, cyclic duty, stall/locked-rotor behavior, regenerative power, brake chopper/resistor duty and DC-bus limits.
- Motor inverter suitability, insulation stress, bearing currents, shaft grounding, low-speed cooling, thermal model and overspeed limits.
- Input supply phase and fault level, transformer/reactor/cable voltage drop, harmonics, fuses/breakers, conductor sizing, filters and protection coordination.
- Ambient temperature, altitude/air pressure, enclosure, contamination, switching frequency, motor-cable length, output filter and every manufacturer derating curve.
- Electrical safety, EMC, functional safety, machine risk assessment, hazardous-area requirements and local regulations.
Често постављана питања
Does a larger motor-kW label prove that a VFD is suitable?
No. Manufacturer kW/hp labels are conditional typical motor associations. Compare the exact continuous and overload current limits for the product, voltage range and duty, then complete the torque, thermal, supply, safety and system checks.
Can I always use 110% for normal duty and 150% for heavy duty?
No. Those values appear in some product families under exact time, recurrence, voltage, power and configuration conditions. Other products and ranges differ. Copy the exact rating from the current manual or selection software for the model under review.
Is motor nameplate current enough?
It is important input, but not always sufficient. ABB’s guide notes that it is only an indication when motor/application derating or a torque profile changes the dimensioning requirement. The complete load study and manufacturer limits govern.
If both ratios are at least 1, is the VFD selected?
No. It means only that the entered continuous current and one overload point do not exceed the entered ratings. The many system checks listed above remain mandatory.