功率因數校正計算器
計算改善功率因數所需的電容組 kVAR 與 μF。Qc = P × (tan φ₁ − tan φ₂)。
結果
無功功率補償
電容值 (μF)
tan φ₁ = tan(acos 0.75) = 0.8819, tan φ₂ = tan(acos 0.95) = 0.3287
Qc = 100 × (0.8819 − 0.3287) = 55.3 kVAR
⚠️ 注意: 請勿將功率因數過補償至超前(leading)狀態。這可能導致電壓上升、與變壓器產生共振,並損壞設備。
PFC adds capacitors to reduce reactive power demand and bring PF closer to 1.0. This reduces current, lowers losses, and avoids utility penalties.
Qc = P × (tan φ₁ − tan φ₂). For μF: C = Qc × 10⁹ / (2π × f × V²). For 3-phase delta, divide by 3 for per-phase capacitance.
Most utilities require ≥0.90. Aim for 0.95–0.98. Avoid overcorrecting above 1.0 (leading PF).
Reduced electricity bills, lower cable current (freeing capacity), reduced I²R losses, better voltage regulation, and utility compliance.
Fixed for constant loads. Automatic (with PF controller) for varying loads — switches capacitor steps to maintain target PF.
本頁所述的操作流程由 Vibromera 團隊使用 Balanset-1A(一款用於現場轉子平衡的便攜式雙通道動平衡儀及振動分析儀)開發並經過實地測試。
專業現場動平衡儀器。已應用於 50 多個國家。
Nikolai Shelkovenko
Nikolai Shelkovenko是一名振動分析工程師,也是Vibromera的創辦人兼執行長。 15年多來,他一直在現場——而非在試驗台上——為旋轉設備進行動平衡校正:粉碎機、工業風機、破碎機、離心機、軸與主軸。正是這些實際工作催生了Balanset系列儀器——它們被設計為一種專業人員可以隨身攜帶到機器旁、在現場獨立使用的工具,而非實驗室設備。 Vibromera成立於2017年,自2023年起總部設於葡萄牙波爾圖。Balanset系列產品的研發、組裝與支援均在此完成。旗艦產品是Balanset-1A,一款用於單平面及雙平面動平衡校正與振動診斷的可攜式分析儀。 Nikolai親自參與客戶支援工作,處理各種棘手的動平衡校正案例,並參與軟體開發。他以任何語言為全球客戶提供服務。