Meet Vibromera.com — our new international website. Visit Vibromera.com →

Recorded values · documented factors · no energization verdict

Documented Insulation-Resistance Normalizer and PI Calculator

Normalize a one-minute winding insulation-resistance reading with the exact multiplication factor from your controlled procedure, calculate the polarization index when a ten-minute reading exists, and compare only with the documented minimum you enter.

No automatic test voltageNo universal pass/fail tableIEEE status disclosed
Recorded test

Leave blank when no valid ten-minute reading was recorded.

Controlled correction and comparison criterion

K must mean: resistance at reference temperature = R₁ × K.

Electrical-safety boundary: this page neither selects a safe DC test voltage nor decides whether equipment may be energized. Insulation testing can damage connected electronics and can leave hazardous stored charge. A qualified person must use the machine and instrument procedures, isolate and lock out the circuit, disconnect incompatible devices, verify absence of voltage, apply the approved test voltage, discharge the winding, and verify it is safe before contact or reconnection.

Documented arithmetic result

Comparison with entered minimum
Normalized one-minute resistance Rref
Entered minimum Rmin
Numeric margin Rref/Rmin
Polarization index R₁₀/R₁
Recorded test voltage

Implemented arithmetic

Rref = R₁ × K
PI = R₁₀ / R₁   (only when a valid R₁₀ is entered)
numeric margin = Rref / Rmin

K is not generated here. Enter the factor whose documented convention explicitly multiplies the measured R₁ to obtain resistance at the entered reference temperature. The former page applied 0.5((40−T)/10) universally, although temperature behaviour depends on the insulation system and the correction convention must be confirmed. The calculator performs an inequality against the supplied Rmin; it does not turn that one comparison into a condition grade, failure diagnosis or energization decision.

IEEE 43 status and scope boundary

The official IEEE page lists IEEE 43-2013, “IEEE Recommended Practice for Testing Insulation Resistance of Electric Machinery,” as Inactive-Reserved since 21 March 2024. IEEE explains that an inactive-reserved standard is no longer being reviewed or assessed for accuracy or relevance. An active P43 revision project, approved 6 December 2023, is intended to supersede IEEE 43-2013 but is not a published replacement standard on the official page as of 12 July 2026. Exact current clauses, winding-specific minimums, test-voltage tables and exceptions therefore remain NEEDS_LICENSED_SOURCE; this page does not reproduce them or call its arithmetic an IEEE formula.

PI and temperature correction

The current Megger BM5200 documentation un Fluke insulation-testing guide support the arithmetic definition PI=R₁₀/R₁. They also emphasize comparable temperatures/correction and trending. They do not justify the former universal labels “dangerous,” “questionable,” “good” and “excellent” for every winding. PI applicability can be limited by insulation system, very high one-minute resistance, instrument range/current limit, leakage paths and the controlled procedure.

Why no automatic test voltage or pass/fail verdict?

The appropriate test voltage and acceptance criteria depend on machine/winding construction, rating, condition, manufacturer instructions and the applicable controlled procedure. Fluke’s motor test safety guidance warns that insulation-test voltage can damage connected electronic controls and describes lockout/tagout, isolation and post-test discharge. A single resistance or PI result cannot identify moisture or contamination by itself and cannot authorize energization.

Required record and review

Retain the raw time-resistance readings, actual test voltage and duration, winding temperature, humidity/environment where required, machine and winding connection, instrument/range/guard use, correction source and convention, previous comparable results, discharge confirmation and deviations from procedure. Resolve a value below the entered criterion under the controlling procedure; do not infer that a value above it proves all insulation or machine conditions acceptable.

© 2024-2026 Vibromera · Scientific review July 2026
Categories:

WhatsApp
Balanset-1A - €1975Jautājiet inženierim