Motor Operating-Point Energy Comparison Worksheet

Compare electrical input energy for two documented motor efficiencies at one common shaft-output operating point and time segment. IE class limits are not treated as the actual efficiency of a specific motor.

Starts blankActual operating pointNo embedded IE tableNo automatic recommendation

Document one equal-output segment

Both efficiencies must apply to the same delivered shaft power,load,supply,temperature and operating conditions. For a varying duty profile,evaluate every supported segment with its own output,efficiencies and hours,then sum the energies outside this worksheet.

Actual mechanical output for this segment—not automatically nameplate rating.
Time spent at the stated output and efficiency.
Documented efficiency at this exact operating point.
Comparable efficiency on the same method and basis.
May be zero for an energy-only comparison;include all intended variable charges explicitly.
A label only;no exchange-rate conversion.
Decision boundary: an IE class limit is a classification threshold under the standard’s rating and test scope,not the measured efficiency of every motor at every load. This worksheet does not include part-load curves,starts,stops,standby,converter,cable,filter,transmission,process or demand-charge effects and does not establish regulatory compliance,life-cycle cost or payback.

Equations implemented

数量EquationUnit/boundary
efficiency fractionη=η%/1000<η≤1;both values apply at the stated operating point.
electrical input powerP=P出去kW;motor terminals on the documented test basis.
input energyE=PhkWh for one constant segment.
motor loss energyEloss=(P−P出去)hkWh;does not include external drive/system losses.
signed differenceΔE=EA−EBPositive only when B uses less input energy under equal output/hours.
cost differenceΔK=ΔE·kEntered cost units;no fixed currency or FX conversion.

Current IEC scope

IEC60034-30-1:2025,Edition2 is the current standard for IE efficiency classes of line-operated,single-speed AC motors rated for sinusoidal50Hz or60Hz supply. Its public scope includes0.12kW to1000kW,50V through1000V,2/4/6/8 poles and specified continuous-operation,ambient and altitude conditions. It excludes power-drive-system efficiency and losses from supply harmonics,cables,filters and frequency converters.

The2025 edition replaced IEC60034-30-1:2014,introduced IE5 limits,new IE5 tables and revised interpolation coefficients. The former page continued to calculate from2014 tables,derived its own IE5 values and linearly interpolated efficiency percentages. Those are not valid substitutes for the current closed tables or interpolation rules.

IEC60034-2-1:2024,Edition3 is current and establishes test methods for determining losses and efficiency of mains-operated rotating machines. A class threshold or catalogue label cannot replace the actual efficiency,test basis and operating-point evidence required by this arithmetic comparison.

IEC TS60034-30-2:2016 separately addresses efficiency classes for variable-speed AC motors not covered by Part30-1. Its public introduction states that application selection depends on actual load/speed operating points and operating time,and that an efficient motor alone does not necessarily produce an efficient power-drive system.

Exact IE tables,interpolation coefficients,tolerances,test-method selection and regulatory mappings remain NEEDS_LICENSED_SOURCE. They are intentionally not reproduced or inferred by this worksheet.

已修正的内容

The former calculator treated IE minimum limits as actual motor efficiency,assumed rated output was delivered continuously,used linear interpolation between closed table rows,clamped every rating below0.75kW or above200kW to an endpoint,and used a derived “20% lower losses” IE5 table after normative IE5 values had been published.

The replacement removes all embedded IE tables,class selectors,pole-speed approximations,presets,defaults,URL/history persistence,hard-coded euros and unsourced1–4-year payback and legal-compliance claims. It accepts only documented efficiencies applicable to the same shaft-output segment and reports a signed comparison without recommending an alternative.

Evidence required for use

  • Use efficiency values obtained or guaranteed on a comparable IEC60034-2-1 or other controlled test basis at the relevant load,supply,speed and temperature.
  • Do not use nameplate IE class alone as η. A motor may exceed its class minimum,and part-load efficiency differs from rated-load efficiency.
  • For variable load/speed,build a segment or time-series model using the applicable efficiency map and include converter and driven-system losses within the chosen boundary.
  • For an investment decision,add installed cost,maintenance,downtime,service life,discounting,tax and uncertainty in a separate documented life-cycle model.