Motor Efficiency Calculator

Compare IE1–IE4 motor efficiency classes per IEC 60034-30-1:2014, plus indicative IE5 (Ultra Premium). Calculate annual energy cost and savings from upgrading to a higher efficiency class.

IEC 60034-30-1IE1 – IE5Energy Savings
Quick presets

Results

Annual Energy Savings
Current Efficiency
Target Efficiency
Kasalukuyang Taunang Enerhiya
Target na Taunang Enerhiya
Kasalukuyang Taunang Gastos
Target na Taunang Gastos
Taunang Pagtipid sa Gastos
Taunang Gastos sa Enerhiya ayon sa IE Class

Energy Consumption Formula

IE Class Minimum Efficiencies (4-pole, 50 Hz)

Power (kW)IE1 (%)IE2 (%)IE3 (%)IE4 (%)
0.7572.179.682.585.7
1.577.282.885.388.2
381.585.587.790.4
7.586.088.790.492.6
1187.689.891.493.3
2289.991.693.094.5
5592.193.594.695.7
11093.394.595.496.3
20094.095.196.096.7

Source: IEC 60034-30-1:2014 (Tables 3, 5, 7, 9), nominal efficiency limits for 4-pole, 50 Hz motors. IE class limits vary by pole count, frequency and rated power — do not apply this 4-pole table to 2-pole or 6-pole motors (the calculator uses separate data sets for each pole count). Limits are defined from 0.12 kW to 1000 kW; ratings above 200 kW use the 200 kW limit, and ratings below 0.75 kW have lower limits than shown here.

About IE5: IEC 60034-30-1:2014 defines only IE1–IE4 for line-operated motors; IE5 (Ultra Premium) appears there only informatively (Annex A) with a target of approximately 20 % lower losses than IE4. Normative IE5 limits were introduced later in IEC 60034-30-1:2025. The IE5 figures used by this calculator are indicative values derived from the 20 %-lower-losses target — consult IEC 60034-30-1:2025 (or IEC TS 60034-30-2 for converter-fed motors) for exact IE5 limits.