Calculate active power P = √3 × V × I × cos φ × η for three-phase motors. Bidirectional — solve for any variable. Also shows apparent & reactive power.

IEC 60034 Bidirectional Power Triangle
Quick presets

Results

Active Power P
Prividna snaga S
Reactive Power Q
Line Current I
Faktor snage / Efikasnost

Formula snage trofaznog motora

The active (real) power consumed or delivered by a three-phase AC circuit is:

  • P — active power (W or kW)
  • VL — fazna napetost (V)
  • IL — fazna struja (A)
  • cos φ — faktor snage (0–1)
  • η — efikasnost motora (0–1)

Power Triangle

Where S je prividna snaga (kVA), P is active power (kW), and Q is reactive power (kVAR).

Praktični primjer

Primjer — Motor od 15 kW na 400 V

Given: P = 15 kW, V = 400 V, cos φ = 0.85, η = 0.91

I = P / (√3 × V × cos φ × η) = 15000 / (1.732 × 400 × 0.85 × 0.91) = 28.0 A

S = √3 × V × I = 1.732 × 400 × 28.0 = 19.40 kVA

Q = √(S² − P²) = √(19.40² − 15²) = 12.30 kVAR

💡 Tip: Pri izračunavanju električne ulazne snage iz nominalnog mehaničkog izlaza motora, uvijek podijelite sa efikasnosti η. Nazivna kW na natpisnoj ploči je obično mehanički izlaz na vratilu.

Vibromera — Prenosivo Balansiranje & Analiza Vibracija
Profesionalni instrumenti i softver za balansiranje na terenu. Koristi se u 50+ zemalja.
Learn More

A reliable **three phase motor power calculator** is an essential tool for electrical engineers and technicians who need to quickly determine active, apparent, and reactive power values without performing manual computations. By inputting known parameters such as line voltage, line current, power factor, and efficiency, this three phase motor power calculator applies the standard formula P = √3 × V × I × cos φ × η to deliver accurate results in seconds. Its bidirectional functionality allows you to solve for any unknown variable, making it invaluable for motor sizing, load analysis, and energy auditing tasks.