Free Engineering Tool

Thermography Temperature Limits

Classify infrared inspection findings per ISO 18434. Enter component type and measured ΔT above reference to get severity classification and recommended action.

ISO 18434NETA MTSIR Inspection
Quick scenarios

Classification

Severity
Measured ΔT
Priority
Recommended Action
Temperature Thresholds for This Component
Temperature Gauge

Electrical Components (NETA MTS)

ΔT (°C)SeverityPriorityAction
1–10Minor4Monitor, repair at convenience
10–35Intermediate3Plan repair at next scheduled outage
35–75Serious2Repair as soon as possible
>75Critical1Immediate action — risk of failure/fire

Mechanical Components

ComponentMinorIntermediateSeriousCritical
Motor body<10°C10–25°C25–40°C>40°C
Bearing housing<10°C10–20°C20–35°C>35°C
Coupling<5°C5–15°C15–25°C>25°C
Steam trap<20°C20–40°C40–60°C>60°C
Insulation<5°C5–15°C15–30°C>30°C
Vibromera — Portable Balancing & Vibration Analysis
Combine vibration analysis with thermography for comprehensive condition monitoring.
Learn More
Categories: