Thermography Temperature Limits
Classify infrared inspection findings per ISO 18434. Enter component type and measured ΔT above reference to get severity classification and recommended action.
ISO 18434NETA MTSIR Inspection
Classification
Severity
—
Measured ΔT
—
Priority
—
Recommended Action
—
Temperature Thresholds for This Component
—
Temperature Gauge
Electrical Components (NETA MTS)
| ΔT (°C) | Severity | Priority | Action |
|---|---|---|---|
| 1–10 | Minor | 4 | Monitor, repair at convenience |
| 10–35 | Intermediate | 3 | Plan repair at next scheduled outage |
| 35–75 | Serious | 2 | Repair as soon as possible |
| >75 | Critical | 1 | Immediate action — risk of failure/fire |
Mechanical Components
| Component | Minor | Intermediate | Serious | Critical |
|---|---|---|---|---|
| Motor body | <10°C | 10–25°C | 25–40°C | >40°C |
| Bearing housing | <10°C | 10–20°C | 20–35°C | >35°C |
| Coupling | <5°C | 5–15°C | 15–25°C | >25°C |
| Steam trap | <20°C | 20–40°C | 40–60°C | >60°C |
| Insulation | <5°C | 5–15°C | 15–30°C | >30°C |